Specially designed pressure/vacuum vent valves should be provided to protect the tank against overpressure or vacuum conditions. Safety should be a primary concern when selecting a storage tank vent system for a specific application. In production operations, this normally means that a safe way of handling vapors that evolve from the liquid must be designed into the system, and air must be excluded from entering the tank and mixing with hydrocarbon in the vapor space.

Configuration

Fixed-roof tanks should be configured to operate with a suitable gas blanketing system that maintains the tank at positive pressures under all operating conditions.

Flame arrestors

Tank vent piping should include flame arrestors such as that shown in Fig. 1, which protect the tank against ignition of the vent gases owing to lightning strike or a discharge of static electricity at the vent location. Where the vent piping is routed to a lit flare system, a constant bleed of purge gas into the vent is required in addition to a flame arrestor. More complex flow devices, such as fluidic seals and molecular seals, are available from several manufacturers to minimize the amount of purge gas needed to assure the flame is not sucked back into the vapor space.

Warnings

Fixed-roof tanks will fail if exposed to excessive internal pressure or extreme vacuum conditions. Regular maintenance of pressure/vacuum vent valves and flame arrestors is critical to the safe operation of any fixed-roof tank. In oil fields, crude oil service flame arrestors can become plugged. A separate pressure/vacuum valve (or specially weighted gauge hatch) set at higher pressures and vacuums than the primary should be installed without a flame arrestor. In the event the flame arrestor becomes plugged, it is better to operate without a flame arrestor then to blow off the roof of the tank.

Design

Many design and operating conditions must be considered when designing a vent piping system. Larger vents may be required on tanks storing heated products or tanks that receive products from a source subject to a surge in pressure or flow. The pressure drop owing to flame arrestors or other vent restrictions must be considered to assure that under design vent conditions the pressure in the tank remains less than the tank design pressure.

Design recommendations can be found in the fifth edition of API Standard 2000 , Venting Atmospheric and Low-Pressure Storage Tanks covering nonrefrigerated and refrigerated storage. The standard presents design guidelines for the determination of venting requirements and types of vents that may be used under normal tank operations and possible emergency conditions (fire exposure).

Sizing

When provided, tank vents should be sized to protect the tank against unusually high internal pressures (venting required) or low pressure vacuum conditions (in breathing or vapor makeup required). Normal operating conditions include:

  • In breathing (vacuum) resulting from maximum outflow of product from the tank.
  • In breathing (vacuum) resulting from contraction of vapors caused by a maximum decrease in atmospheric temperature.
  • Out breathing (pressure) resulting from flashing of hydrocarbons as liquid flows from a higher pressure source into the tank. In production operations this can be the largest source of vent vapors. The flow rate is process specific and not addressed in the API Standard 2000.
  • Out breathing (pressure) resulting from maximum inflow of product into the tank, hydrocarbon flash vapors, and maximum product evaporation caused by the inflow.
  • Out breathing (pressure) resulting from expansion and evaporation caused by a maximum increase in atmospheric temperature.
  • Out breathing (pressure) resulting from fire exposure.

General references

Evaporative Loss Measurement. 1997. In Manual of Petroleum Measurement Standards, Ch. 19, Sec. 2-E. Washington, DC: API.

API RP12R1, Setting, Maintenance, Inspection, Operation, and Repair of Tanks in Production Service, fifth edition. 1997. Washington, DC: API.

API RP575, Inspection of Atmospheric and Low-Pressure Storage Tanks, first edition. 1995. Washington, DC: API.

API RP651, Cathodic Protection of Aboveground Petroleum Storage Tanks, second edition. 1997. Washington, DC: API.

API RP652, Lining of Aboveground Petroleum Storage Tank Bottoms, first edition. 1991. Washington, DC: API.

API RP2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents, fifth edition. 1991. Washington, DC: API.

API Spec. 12B, Bolted Tanks for Storage of Production Liquids, fourteenth edition. 1995. Washington, DC: API.

API Spec. 12D, Field-Welded Tanks for Storage of Production Liquids, tenth edition. 1994. Washington, DC: API.

API Spec. 12F, Shop-Welded Tanks for Storage of Production Liquids, eleventh edition. 1994. Washington, DC: API.

API Standard 650, Welded Steel Tanks for Oil Storage, tenth edition. 1998. Washington, DC: API.

API Standard 653, Tank Inspection, Repair, Alteration, and Reconstruction, second edition. 1995. Washington, DC: API.

API Standard 2000, Venting Atmospheric and Low-Pressure Storage Tanks (Nonrefrigerated and Refrigerated), fifth edition. 1998. Washington, DC: API.

API Standard 620, Design and Construction of Large, Low-Pressure Storage Tanks, tenth edition. 2002. Washington, DC: API.

Noteworthy papers in OnePetro

Use this section to list papers in OnePetro that a reader who wants to learn more should definitely read

External links

Use this section to provide links to relevant material on websites other than PetroWiki and OnePetro

See also

Oil storage

Fixed roof tanks

Tank breathing

Floating roof tanks

Controlling liquid leaks from tanks

Site considerations for production tanks

Tank battery

PEH:Oil Storage