You must log in to edit PetroWiki. Help with editing

Content of PetroWiki is intended for personal use only and to supplement, not replace, engineering judgment. SPE disclaims any and all liability for your use of such content. More information


Power factor and capacitors: Difference between revisions

PetroWiki
Jump to navigation Jump to search
 
No edit summary
 
(2 intermediate revisions by the same user not shown)
Line 1: Line 1:
The electrical power required to drive a motor has three components: reactive power (''P''<sub>''r''</sub>, kVAR), active power (''P''<sub>''a''</sub>, kW), and apparent power (''P''<sub>''ap''</sub>, kVA). The active power is the actual amount of work done by the motor and measured for billing purposes. The reactive power is the power required to magnetize the motor winding or to create magnetic flux, and is not recordable. The apparent power is the vector sum of kilowatts and kilovars and is the total amount of energy furnished by the utility company.  
The electrical power required to drive a motor has three components: reactive power (''P''<sub>''r''</sub>, kVAR), active power (''P''<sub>''a''</sub>, kW), and apparent power (''P''<sub>''ap''</sub>, kVA). The active power is the actual amount of work done by the motor and measured for billing purposes. The reactive power is the power required to magnetize the motor winding or to create magnetic flux, and is not recordable. The apparent power is the vector sum of kilowatts and kilovars and is the total amount of energy furnished by the utility company.


==Power relationships==
== Power relationships ==
The power triangles shown in '''Fig. 1''' illustrate the relationships between these terms.


<gallery widths=300px heights=200px>
The power triangles shown in '''Fig. 1''' illustrate the relationships between these terms.
 
<gallery widths="300px" heights="200px">
File:Vol3 Page 474 Image 0001.png|'''Fig. 1—Power triangles (courtesy of AMEC Paragon).'''
File:Vol3 Page 474 Image 0001.png|'''Fig. 1—Power triangles (courtesy of AMEC Paragon).'''
</gallery>
</gallery>


==Power factor==
== Power factor ==
 
The power factor (''F''<sub>''p''</sub>) is the ratio of active power to apparent power:
The power factor (''F''<sub>''p''</sub>) is the ratio of active power to apparent power:


[[File:Vol3_page_474_eq_001.png]]('''Eq. 1''')
[[File:Vol3 page 474 eq 001.png|RTENOTITLE]]('''Eq. 1''')


The power factor is "leading" in loads that are more capacitive and "lagging" in loads that are more inductive (e.g., motor or transformer windings). In a purely resistive load, ''F''<sub>''ops''</sub> = 1 (unity), such that ''P''<sub>''a''</sub> = ''P''<sub>''ap''</sub> (kW = kVA) and no reactive power is present. When ''F''<sub>''p''</sub> < unity, reactive power is present and more power is required to produce work, as seen in the following equation:
The power factor is "leading" in loads that are more capacitive and "lagging" in loads that are more inductive (e.g., motor or transformer windings). In a purely resistive load, ''F''<sub>''ops''</sub> = 1 (unity), such that ''P''<sub>''a''</sub> = ''P''<sub>''ap''</sub> (kW = kVA) and no reactive power is present. When ''F''<sub>''p''</sub> < unity, reactive power is present and more power is required to produce work, as seen in the following equation:


[[File:Vol3_page_474_eq_002.PNG]]('''Eq. 2''')
[[File:Vol3 page 474 eq 002.PNG|RTENOTITLE]]('''Eq. 2''')
 
== Reactive power ==


==Reactive power==
The reactive power of a motor is approximately the same from no load to full load. When a motor is operating at full load, the active/reactive power ratio is high, and thus the power factor of the motor is high. A lightly loaded motor has a low active/reactive power ratio, which causes the power factor to be low. At low power factors, more power will be required from the utility company than actually is needed by the load. This translates into higher energy cost and the need for larger generation units and transformers. Some utility companies charge a substantial penalty to their customers for low power factors (generally < 0.95). Also, low power factors might cause more voltage drop in the system, which causes the motors to operate sluggishly and the lights to dim.
The reactive power of a motor is approximately the same from no load to full load. When a motor is operating at full load, the active/reactive power ratio is high, and thus the power factor of the motor is high. A lightly loaded motor has a low active/reactive power ratio, which causes the power factor to be low. At low power factors, more power will be required from the utility company than actually is needed by the load. This translates into higher energy cost and the need for larger generation units and transformers. Some utility companies charge a substantial penalty to their customers for low power factors (generally < 0.95). Also, low power factors might cause more voltage drop in the system, which causes the motors to operate sluggishly and the lights to dim.  


It is essential that the power factor of the system be maintained as high as possible (close to unity). Removing the reactive power from the system can make this possible. Power-factor-correction capacitors are used for this purpose. A motor requires inductive or lagging reactive power for magnetizing. Capacitors provide capacitive or leading reactive power that cancels out the lagging reactive power when used for power-factor improvement. The power triangles in '''Fig. 2''' show how capacitors can improve the power factor for a motor. The improved power factor changes the current required from the utility company, but not the one required by the motor.
It is essential that the power factor of the system be maintained as high as possible (close to unity). Removing the reactive power from the system can make this possible. Power-factor-correction capacitors are used for this purpose. A motor requires inductive or lagging reactive power for magnetizing. Capacitors provide capacitive or leading reactive power that cancels out the lagging reactive power when used for power-factor improvement. The power triangles in '''Fig. 2''' show how capacitors can improve the power factor for a motor. The improved power factor changes the current required from the utility company, but not the one required by the motor.


<gallery widths=300px heights=200px>
<gallery>
File:Vol3 Page 476 Image 0001.png|'''Fig. 2—Power triangle showing power factor correction.'''<ref name="r1" />
File:Vol3 Page 476 Image 0001.png|Fig. 2—Power triangle showing power factor correction.
</gallery>
</gallery><ref name="r1">H.B. Bradley, ed. 1987. ''Petroleum Engineering Handbook''. Richardson, Texas: SPE.</ref>
 
== Capacitors ==


==Capacitors==
Capacitors should not be selected as a means of correcting poor power factors that are the result of oversized motors or unbalanced pumping units. Choosing a capacitor for this purpose might cause overcorrection, which can result in a leading power factor. A leading power factor, in turn, might cause overvoltages that would cause control-component failure or power-cable failure. This potential problem generally is avoided by connecting the capacitors downstream of the motor contactors and switching them on and off, along with the motor contactors.
Capacitors should not be selected as a means of correcting poor power factors that are the result of oversized motors or unbalanced pumping units. Choosing a capacitor for this purpose might cause overcorrection, which can result in a leading power factor. A leading power factor, in turn, might cause overvoltages that would cause control-component failure or power-cable failure. This potential problem generally is avoided by connecting the capacitors downstream of the motor contactors and switching them on and off, along with the motor contactors.  


Power factor correction capacitors could be applied to each individual motor to correct the power factor of that motor, or could be a single unit connected to the main bus of the switchgear. In the latter case, the unit should have power-factor-sensing circuits that automatically determine the amount of capacitance required for maintaining a preset power factor. The required amount of capacitors are automatically added to or removed from the switchgear bus to maintain the required power factor.  
Power factor correction capacitors could be applied to each individual motor to correct the power factor of that motor, or could be a single unit connected to the main bus of the switchgear. In the latter case, the unit should have power-factor-sensing circuits that automatically determine the amount of capacitance required for maintaining a preset power factor. The required amount of capacitors are automatically added to or removed from the switchgear bus to maintain the required power factor.


The cyclic kW load on a pumping-unit motor can cause the power factor to vary from 1.0 to near zero if excessive adverse pumping conditions exist.
The cyclic kW load on a pumping-unit motor can cause the power factor to vary from 1.0 to near zero if excessive adverse pumping conditions exist.


==Nomenclature==
== Nomenclature ==
 
{|
{|
|''F''<sub>''p''</sub>
|=
|power factor, cos ''θ''
|-
|-
|''P''<sub>''a''</sub>  
| ''F''<sub>''p''</sub>
|=  
| =
|active power, kW
| power factor, cos ''θ''
|-
|-
|''P''<sub>''ap''</sub>  
| ''P''<sub>''a''</sub>
|=  
| =
|apparent power, kVA  
| active power, kW
|-
| ''P''<sub>''ap''</sub>
| =
| apparent power, kVA
|}
|}


==References==
== References ==
<references>
 
<ref name="r1">H.B. Bradley, ed. 1987. ''Petroleum Engineering Handbook''. Richardson, Texas: SPE. </ref>
<references />
</references>
 
== Noteworthy papers in OnePetro ==


==Noteworthy papers in OnePetro==
Use this section to list papers in OnePetro that a reader who wants to learn more should definitely read
Use this section to list papers in OnePetro that a reader who wants to learn more should definitely read


==External links==
== External links ==
 
Use this section to provide links to relevant material on websites other than PetroWiki and OnePetro
Use this section to provide links to relevant material on websites other than PetroWiki and OnePetro


==See also==
== See also ==
[[Electrical grounding]]
 
[[Electrical_grounding|Electrical grounding]]


[[Electrical distribution systems]]
[[Electrical_distribution_systems|Electrical distribution systems]]


[[Electrical systems]]
[[Electrical_systems|Electrical systems]]


[[Hazardous area classification for electrical systems]]
[[Hazardous_area_classification_for_electrical_systems|Hazardous area classification for electrical systems]]


[[Alternating current motors]]
[[Alternating_current_motors|Alternating current motors]]


[[Induction motors]]
[[Induction_motors|Induction motors]]


[[Synchronous motor]]
[[Synchronous_motor|Synchronous motor]]


[[Motor specifications]]
[[Motor_specifications|Motor specifications]]


[[NEMA motor characteristics]]
[[NEMA_motor_characteristics|NEMA motor characteristics]]


[[Alternating current motor drives]]
[[Alternating_current_motor_drives|Alternating current motor drives]]


[[Motor enclosures]]
[[Motor_enclosures|Motor enclosures]]


[[PEH:Electrical Systems]]
[[PEH:Electrical_Systems]]

Latest revision as of 19:57, 1 June 2015

The electrical power required to drive a motor has three components: reactive power (Pr, kVAR), active power (Pa, kW), and apparent power (Pap, kVA). The active power is the actual amount of work done by the motor and measured for billing purposes. The reactive power is the power required to magnetize the motor winding or to create magnetic flux, and is not recordable. The apparent power is the vector sum of kilowatts and kilovars and is the total amount of energy furnished by the utility company.

Power relationships

The power triangles shown in Fig. 1 illustrate the relationships between these terms.

Power factor

The power factor (Fp) is the ratio of active power to apparent power:

RTENOTITLE(Eq. 1)

The power factor is "leading" in loads that are more capacitive and "lagging" in loads that are more inductive (e.g., motor or transformer windings). In a purely resistive load, Fops = 1 (unity), such that Pa = Pap (kW = kVA) and no reactive power is present. When Fp < unity, reactive power is present and more power is required to produce work, as seen in the following equation:

RTENOTITLE(Eq. 2)

Reactive power

The reactive power of a motor is approximately the same from no load to full load. When a motor is operating at full load, the active/reactive power ratio is high, and thus the power factor of the motor is high. A lightly loaded motor has a low active/reactive power ratio, which causes the power factor to be low. At low power factors, more power will be required from the utility company than actually is needed by the load. This translates into higher energy cost and the need for larger generation units and transformers. Some utility companies charge a substantial penalty to their customers for low power factors (generally < 0.95). Also, low power factors might cause more voltage drop in the system, which causes the motors to operate sluggishly and the lights to dim.

It is essential that the power factor of the system be maintained as high as possible (close to unity). Removing the reactive power from the system can make this possible. Power-factor-correction capacitors are used for this purpose. A motor requires inductive or lagging reactive power for magnetizing. Capacitors provide capacitive or leading reactive power that cancels out the lagging reactive power when used for power-factor improvement. The power triangles in Fig. 2 show how capacitors can improve the power factor for a motor. The improved power factor changes the current required from the utility company, but not the one required by the motor.

[1]

Capacitors

Capacitors should not be selected as a means of correcting poor power factors that are the result of oversized motors or unbalanced pumping units. Choosing a capacitor for this purpose might cause overcorrection, which can result in a leading power factor. A leading power factor, in turn, might cause overvoltages that would cause control-component failure or power-cable failure. This potential problem generally is avoided by connecting the capacitors downstream of the motor contactors and switching them on and off, along with the motor contactors.

Power factor correction capacitors could be applied to each individual motor to correct the power factor of that motor, or could be a single unit connected to the main bus of the switchgear. In the latter case, the unit should have power-factor-sensing circuits that automatically determine the amount of capacitance required for maintaining a preset power factor. The required amount of capacitors are automatically added to or removed from the switchgear bus to maintain the required power factor.

The cyclic kW load on a pumping-unit motor can cause the power factor to vary from 1.0 to near zero if excessive adverse pumping conditions exist.

Nomenclature

Fp = power factor, cos θ
Pa = active power, kW
Pap = apparent power, kVA

References

  1. H.B. Bradley, ed. 1987. Petroleum Engineering Handbook. Richardson, Texas: SPE.

Noteworthy papers in OnePetro

Use this section to list papers in OnePetro that a reader who wants to learn more should definitely read

External links

Use this section to provide links to relevant material on websites other than PetroWiki and OnePetro

See also

Electrical grounding

Electrical distribution systems

Electrical systems

Hazardous area classification for electrical systems

Alternating current motors

Induction motors

Synchronous motor

Motor specifications

NEMA motor characteristics

Alternating current motor drives

Motor enclosures

PEH:Electrical_Systems